Table 7 High fault short circuit ratings, using Bul. 140M, circuit breakers, per UL508 and CSA 22.2 No.14
Contactor Cat.
E1 Plus Cat. No.
ED1ED, ED1FD,
EEED, EEFD
193
EEEE, EEFE,
EEGE
Table 8 High fault short circuit ratings, using Bul. 140U, circuit breakers, per UL508 and CSA 22.2 No.14
Contactor Cat.
E1 Plus Cat. No.
ED1ED, ED1FD,
EEED, EEFD
193
EEEE, EEFE,
EEGE
Table 9 Group installation short circuit ratings
Catalog Nos. 193/592-EE and ED1 noted below have the following group installation short circuit ratings
when used with the specified contactors and branch circuit protection.
Overload Relay
-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
193
-ED1EB.
-EEAB, -EEBB, EECB,
-EEDB, -EEEB.
-ED1AB, -ED1BB,
-ED1CB, -ED1DB,
193
-ED1EB.
-EEAB, -EEBB, - EECB,
-EEDB, -EEEB.
E
K
CONTACTOR CAT. NO.
E1 PLUS CAT. NO.
100-C09, -C12,
193-ED1_B, 193*-EE_B
-C16, -C23
100-C30, -C37
100-C43
100-C60, -C72, -C85, -C97
300-AO_, -BO_
300-CO_
41053-358-01
DIR 41053-358 (Version 09)
Printed in U.S.A.
Max. starter
Max. available fault current (kA)
At 480V
No.
FLC (A)
100-C30
30
100-C30
30
100-C37
37
100-C43
43
100-C60
60
100-C72
72
100-C85
85
Max. starter
Max. available fault current (kA)
At 480V
No.
FLC (A)
100-C30
30
100-C37
37
100-C43
43
100-C60
60
100-C72
72
100-C85
85
Max. Available
Contactor
Fault Current
100-C09,
100-C12,
5,000
100-C16
100-C09,
100-C12,
30,000
100-C16
A
F
G
B
D
A
mm
45
(in)
(1.76)
mm
45
(in)
(1.76)
193-ED1_D,
193*-EE_D
mm
54
(in)
(2.12)
mm
72
193*-EE_E
(in)
(2.83)
mm
45
193-ED1_D,
(in)
(1.76)
193*-EE_D
mm
72
193*-EE_E
(in)
(2.83)
Circuit Breaker Cat.
At 600Y/347 V
65
30
140M-H8P-C30
65
30
140M-H8P-C50
65
30
140M-H8P-C50
65
30
140M-H8P-C50
65
30
140M-H8P-D10
65
30
140M-H8P-D10
65
30
140M-H8P-D10
Circuit Breaker Cat.
At 600V
50
25
140U-H*C3-C50
50
25
140U-H*C3-C50
50
25
140U-H*C3-C50
65
25
140U-H*C3-D11
65
25
140U-H*C3-D11
65
25
140U-H*C3-D11
Max. Voltage
UL Fuse
Class RK5
480
60 Amp.
Class J
480
100 Amp
B
C
D
146.6
85.2
24.5
(5.77)
(3.35)
(.96)
24.5
146.6
101.2
(5.77)
(3.98)
(.96)
101.2
24.5
146.6
(5.77)
(3.98)
(.96)
192
120.4
29
(7.57)
(4.74)
(1.14)
101.2
24.5
146.6
(5.77)
(.96)
(3.98)
192
29
120.4
(7.57)
(4.74)
(1.14)
Max. Circuit Breaker
No.
Current (A)
30
50
50
50
100
100
100
Max. Circuit Breaker
No.
Current (A)
50
50
50
110
110
110
J
H
C
E
F
G
H
13.9
35
60
86.5
(.55)
(1.38)
(2.36)
(3.40)
13.9
35
60
104
(.55)
(1.38)
(2.36)
(4.09)
104
18.4
45
60
(.74)
(1.77)
(2.36)
(4.09)
23.8
55
100
126
(.94)
(2.16)
(3.94)
(4.94)
13.9
104
35
60
(.55)
(1.38)
(2.36)
(4.09)
23.8
55
100
126
(.94)
(2.16)
(3.94)
(4.94)
J
K
2
4.5
(.08)
(.17)
2
4.5
(.17)
(.08)
4.5
2
(.08)
(.17)
2
5.4
(.21)
(.08)
2
4.5
(.08)
(.17)
2
5.4
(.21)
(.08)