GB
MAS200 ANTI CRUSHING CARD
This optional MAS200 briefly closes the gates after detecting a mechanically locked motor.. When this hap-
pens LED L1 (det. 3 of fig. 1) lights up for a few seconds.
The movement following the above activation is in the opposite direction to that being carried out prior to
locking.
For example: if the motor becomes locked during gate opening, it automatically carries out a short closing
movement and upon pressing the button P/P restarts closing of the gate.
NOTES
- The module MAS200 is calibrated for each type of motor, see MAS200 instructions.
- The anti-crushing device does not activate during slowdown.
- If a motor is not connected or incorrectly connected, the module MAS200 activates continuously.
POWER CONTROL
The foto test is a special function for checking the efficiency of the photocells prior to every movement.
For the foto test to work, the system must have two power supply lines for the photocells: the first is con-
nected to terminals 12 and 13 and powers the receivers, while the second is connected to terminals 14 and
15 and powers the transmitters.
The foto test function must be enabled by putting the dipswitch No. 7 to the ON position (det. 11 of fig. 1).
In practice the control unit cuts off the power supply, to the transmitter, for an instant and checks that the
receivers change state.
If everything is in correct and in working order, the motors start and gate movement begins; if the receiver
has a problem, the cycle is stopped and indicated by several fast blinks of the open gate indicator light.
NOTES
- The foto test also operates with the photocell 3 (wild input) and if several photocells are con-
nected with the contact in series.
- With the foto test enabled and the control unit in stand-by, the photocell transmitters are not pow-
ered and the inputs FT1 and FT2 are open (LEDs off). In this condition, it is still possible to check
photocell operation by short-circuiting the photocell "Test" pins (det. 13 of Fig. 1).
TRIAC TEST
The control unit T200 controls the motors through the TRIAC.
This component is essential to the system operation and safety.
If there is an anomaly, the control unit locks and the gate open indicator light blinks slowly.
NOTE:
Should the motors be incorrectly connected or the anti-crushing card MAS200 is not connected the
TRIAC fails safe.
33
E
TAB.1
MOR.
MOR.
DISPOSITIVO
V
n.
n.
1
Motor M1
230Vac
2
Motor M1
230Vac
3
Motor M1
230Vac
2
3
Condensador
230Vac
4
Motor M2
230Vac
5
Motor M2
230Vac
6
Motor M2
230Vac
5
6
Condensador
230Vac
7
8
Luz intermitente
230Vac
9
8
Lámpara
230Vac
10
11
Línea
230Vac
12
13
Auxiliares
24Vac
Transmisores
14
15
24Vac
fotocélula/s
15
16
Luz de aviso
24Vac
17
18
Electrocerradura
12Vcc
20
19 o 25 Contacto N.C.
21
19 o 25 Contacto N.C.
22
19 o 25 Contacto N.C.
23
19 o 25 Contacto N.C.
Contacto N.C. o
24
19 o 25
Bóton N.A.
Contacto N.C. o
26
25 o 31
Bóton N.A.
27
25 o 31 Contacto N.C.
I
FUNCIÓN
NOTE
max
El motor M1 se cierra con retardo
4A
Común M1
(para excluir el retardo, véase el dip-
4A
Cierra M1
switch nº 11). En el caso de cancelas
batientes, el motor M1 debe controlar
4A
Abre M1
la hoja con la electrocerradura.
Véanse las notas del motor.
4A
Toma de fuerza m. M1
El motor M2 se abre con retardo
4A
Común M2
(para excluir el retardo, véase el dip-
4A
Cierra M2
switch nº 11).
4A
Abre M2
Véanse las notas del motor.
4A
Toma de fuerza m. M2
Encendida cuando el motor está en acción. El
Indicatore
1A
encendido puede ser anticipado (parpadeo
de movimiento
previo). Véase el dip-switch funciones nº 5.
Encendida desde el inicio de la maniobra
1A
Luz interior
hasta 3 minutos después del cierre com-
Es preciso conectarla a la línea de
Alimentación
230 V c.a. Véase el apartado
6,3A
centralina
"CONEXIONES ELECTRICAS".
Permanente para la alimentación de
150mA Alimentación
fotocélulas y dispositivos auxiliares.
Alimentación tran.
Alimentación para transmisores fotocé-
150mA
lula (si se utiliza la función Foto test).
para foto-test
Debe utilizarse una bombilla de 24 V - 2 W
100mA Cancela abierta
máx. Véase el texto.
Se activa, durante algunos segun-
dos, cada vez que comienza la fase
1A
Bloqueo mecánico
de apertura.
Fin de carrera
Conectar esta entrada al común, si
no se utiliza.
Cierra (M1)
Fin de carera
Conectar esta entrada al común, si
no se utiliza.
Abre (M1)
Durante la fase de cierre, invierte la mar-
Fotocélula 1**
cha. Conectar esta entrada al común, si no
se utiliza.
Bloqueo temporal de la maniobra en fase
de apertura. Durante la fase de cierre,
Fotocélula 2**
invierte la marcha. Esta entrada debe
conectarse al común si no es utilizada.
Véase el dip-switch funciones nº 3 y 4.
Jolly 2
Si no se utiliza esta entrada, los dips
nº 3 y nº 4 deben ponerse en OFF.
Véase el dip-switch funciones nº 3 y 4.
Jolly 1
Si no se utiliza esta entrada, los dips
nº 3 y nº 4 deben ponerse en OFF.
Hace invertir la marcha durante algunos
segundos y la central de mando se blo-
Barra fija
quea. Esta entrada debe conectarse al
común si no es utilizada.
78