9.4.2
Configuration via web user interface
AVISO
In addition to the parameters in the chapterMenu [Ver capítulo 9.4.1} Página 39], additional parame-
ters are available and accessible via the web user interface. To do so, enable Remote config in
Network under Webserver and enter the device IP address into your browser.
Operating settings
1
2
3
4
CC Tensión inicial
1
2
3
4
Reg. tensión const.
1
2
3
4
Resistencia aisl.
1
2
3
4
Vigilancia trifásica
1
2
3
4
4
On / Off
FRT (Fault Ride Th-
1
2
3
4
4
rough)
Página 50
Action in this menu/meaning
AVISO: Grid operators require shutdown of the device with
standalone grid detection.
F Further parameterisation is possible via the web interface.
AVISO: Display of grid faults.
F To show the last 5 grid fault messages, press the Show button.
F Further parameterisation is possible via the web interface
Open the menu: Press the right arrow button or the OK button.
Displays the type designation of the device. If feed-in power is actively
limited: display maximum power in kW.
Displays the installed software version.
Displays the serial number of the device.
Displays the selected country setting. Optional: Displays the grid type if
a grid type has been selected.
The display shows information about the device manufacturer.
AVISO: Options for advanced setting of the operating parame-
ters.
The device begins feed-in as soon as this DC voltage is present.
F Set the starting voltage.
AVISO: Option to disable the MPP seek mode in order to ope-
rate the device with a constant DC voltage.
1. Activate or disable the constant voltage controller.
2. Set value for constant voltage controller.
F Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
AVISO: The device is equipped with redundant 3-phase moni-
toring. If the grid voltage exceeds or drops below the configu-
red values, the device switches off. The minimum switch-off
threshold can be set in 1 V increments.
F Activate or disable monitoring.
AVISO: The device supports dynamic grid stabilization (Fault
Ride-Through).
Manual
Kaco blueplanet 29.0TL3