9 | Configuration and operation
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
cos-phi(P/Plim)
1
2
3
4
4
Settling time
1
2
3
4
4
1s – 120 s
Tensión Lock-In
1
2
4
4
3
23V – 287V
Tensión Lock-Out
4
1
2
3
4
23V – 287V
Núm. de pu. de apoyo
1
2
3
4
4
2 - 10
1. punto de apoyo ...
1
2
3
4
4
10. punto de apoyo
Voltage | Reactive
power | Excitation
0-100%
1 – 0.3
Over-excited | un-
der-excited
10 p. apoyo Q(U)
1
2
3
4
4
Settling time
1
2
3
4
4
1s – 120 s
Potencia Lock-In
1
2
3
4
4
0 – 100% S
Potencia Lock-Out
1
2
3
4
4
0-100% S
Hora Lock-In
1
2
3
4
4
0 s – 60 s
Hora Lock-Out
1
2
3
4
4
0 s – 60 s
Página 48
Action in this menu/meaning
AVISO: More detailed information about the procedure can be
found at:
Reactive power control [Ver capítulo 10.1} Página 60]
F Open the menu: Press the Right arrow button or Enter
button.
F Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient res-
ponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.
F Set the voltage above which control is activated.
F Set the voltage below which control is deactivated.
AVISO: The maximum number of configurable nodes depends
on the selected grid type.
F Specify the number of nodes for the cos ϕ /(p/pn).
F Power factor for 1st ,10th ... node as a percentage of the maximum
power.
F Specify the AVISO: cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of pha-
se shift.
F Open the menu: Press the Right arrow button or Enter
button.
AVISO: More detailed information about the procedure can be
found at:
Reactive power control [Ver capítulo 10.1} Página 60]
F Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient res-
ponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.
F Set the active power as % of rated power above which control is acti-
vated.
max
F Set the active power as % of rated power below which control is de-
activated.
max
F Set the length of time that the active power must remain below the
lock-in power level before control is activated.
F Set the length of time that the active power must remain below the
lock-out power level before control is deactivated.
Manual
Kaco blueplanet 29.0TL3