Manual
Country-
Me-
Display/
spec.
nu
Setting
Settings
le-
vel
Puerto
1
2
3
4
4
Estado conexión
1
2
3
4
4
Parámetros
1
2
3
4
4
Password protection
1
2
3
4
4
Status
On/Off
País
1
2
3
4
CH, DE, ES,
Tipo red/Directiva
1
2
3
4
FR, GB, GR,
IT, JO, JP,
LU, TH, ZA
UD
Tensión nom. de red
1
2
3
4
Parámetros de red
1
2
3
4
AT, BG, CZ,
Desc. sobretensión Va-
1
2
3
4
FR-OLD,
lor medio 10 min.
FR-VFR13,
FR-VFR14,
IE, JP, NL,
PL, PT, TR,
TW, UD
BE CH-NS
Desc. sobretensión Va-
1
2
3
4
CY DE-NS
lor medio 10 min. Prot.
DK LU-NS
por contraseña
AT FR-OLD
Caída de tensión
1
2
3
4
FR-VFR13
FR-VFR14
JP-50HZ
JP-60HZ
UD
Kaco blueplanet 29.0TL3
Configuration and operation | 9
Action in this menu/meaning
F Set network port.
Indicates the status of the network connection.
F Press the Right arrow button or Enter button.
AVISO: The device does not display the "Parameters" menu in
the standard configuration. To display the Parameters menu:
1. Open the menu.
2. Simultaneously hold down the Up and Down buttons for se-
veral seconds.
AVISO: Opportunity to set password protection.
F Selecting "yes" initiates a password request for the entire menu
item: Parameters.
AVISO: This option influences the country-specific operating
settings of the device. Please consult KACO service for further
information.
1. Enter the four-digit password using the 4-way button. The
password is unit-specific.
2. Confirm the entry with the Enter button.
3. Set the desired country setting.
F Select the grid type for the device's installation location.
F Set the specified grid voltage for the site where the unit is used (ple-
ase contact KACO Service)
F Open the menu: Press the Right arrow button or Enter
button.
1. Specify the shutdown threshold for overvoltage shutdown.
ð The 10-minute average for the measured voltage as per
EN50160 is used.
2. Set period from occurrence of the fault to shutdown of the de-
vice.
1. Activate or disable password protection.
2. Specify the shutdown threshold for overvoltage shutdown.
ð The 10-minute average for the measured voltage as per
EN50160 is used.
3. Set period from occurrence of the fault to shutdown of the de-
vice.
AVISO: The voltage drop between the device and the feed-in
meter is added to the limit value that was set for grid shut-
down according to EN 50160. The limit value can be set to
0-11 Volt increments.
F Specify the shutdown value for the voltage drop (0-11 Volt).
Página 43