Installation instructions

Use the Festo cable sockets type ASI−SD−FK... for connect
ing the valve terminals. You thereby comply with protec
tion class IP65. Proceed as follows.
1. Connect the earth connection (M3) with low impe
dance to the earth potential.
2. Press the AS−Interface cable into the upper part of the
cable socket.
3. Make sure that the AS−Interface cable is free of tension.
4. Place the cable socket in position and screw it tight
(max. 0.3 Nm).
1
AS−Interface cable
2
Cable socket type
ASI−SD−FK or type
ASI−SD−FK180
3
Cable cap type
ASI−KK−FK
Please note with branch lines:
the total maximum length of the AS−Interface bus:
100 m (without repeater/extender).
the cable length of the load voltage connection
(depends on the ccurrent consumption of the valve
terminal and the fluctuations in the load voltage).
seal unused cable ends with the Festo cable cap type
ASI−KK−FK or the cable sleeve type ASI−KT−FK. In this
way you will avoid leakage currents and comply with
protection class IP65.