ELECTRICAL INSTALLATION
Power Wiring Connections

Power Circuit and Motor Connections

Drive is suitable for use on a circuit capable of delivering not more than 5000 RMS symmetrical amperes,
250 volts maximum.
Verify that the dedicated branch circuit for the drive is equipped with a properly-sized circuit breaker. Refer
to
"Input Wire and Fuse Sizing" on page 17
Verify that the power has been shut off at the main breaker. Follow Lockout-Tagout procedures.
1.
Feed the motor leads through the opening on the bottom right side of the drive and connect them to
the terminal block positions marked
2. Feed the input power leads through the larger opening on the bottom left side of the drive. Connect
single-phase 230 V wires to L1, L2, and
These connectors accept wire sizes from 6 to 20 AWG and should be tightened to 15 in-lbs (1.7 Nm).
20
for minimum breaker size.
(Green Ground Wire), RED, YEL, and BLK.
.