Display Of Operating Data And Counters; Checks; Chimney Sweeper Function - Sime Brava One HE 25 ErP Manual De Instalación Y Mantenimiento

Calderas murales de condensación
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
3.5

Display of operating data and counters

Once the boiler is operating a qualified technician can view the
operating data "In" and the counters "CO" as follows:
– from the operating screen in the mode enabled at that
moment (WINTER
n
or SUMMER
– go into "INFO" by pressing the buttons
for more than 3 seconds until "In" appears alternating
time
with "0.0" (information number) and "25" (eg. value)
From this point, the technician has 2 options:
– scroll through the list of "info" and "counters" by pressing the
button
>
. This way, scrolling will be in sequence
– display the "activated alarms" (no more than 10) by pressing
the button
<
. Once in this section, proceed with button
When all the values have been displayed, exit the menu by
pressing and holding down the button
seconds until the initial screen is displayed.
TABLE OF INFORMATION DISPLAYED
Type
No.
Description
In
0.0
SW version
In
0.1
External sensor
Delivery sensor
In
0.2
temperature
In
0.3
Smoke probe
Domestic hot water
In
0.4
sensor temperature
In
0.5
AUX auxiliary sensor
Actual heating SET
In
0.6
temperature
In
0.7
Power level
In
0.8
Flow meter rate
Water pressure
In
0.9
transducer reading (if
resent)
Display of current fan
In
1.0
revolutions
l
)
>
and
<
at the same
>
or
<
.
o
for approximately 5
Range
U/M
Step
- 9 ..
°C
1
99
- 9 ..
°C
1
99
- 9 ..
°C
1
99
- 9 ..
°C
1
99
- 9 ..
°C
1
99
Par. 13
... Par.
°C
1
14
0 .. 99
%
1
0 .. 99
l/min
0.1
0 .. 99
bar
0.1
0 .. 99 RPM x 100
1
TABLE OF COUNTER DISPLAYED
Type
No.
Description
total no. of boiler
CO
0.0
operating hours
total no. of burner
CO
0.1
operating hours
total no. of burner
CO
0.2
ignitions
CO
0.3
total no. faults
total no. of times
CO
0.4
installer parameters
"tS"accessed
total no. of times
CO
0.5
OEM parameters
accessed
time unitl next
CO
0.6
maintenance
intervention
total no. of
CO
0.7
calibrations
TABLE OF ACTIVATED ALARMS/FAULTS
Type
No.
Description
AL
00
Last activated alarm/fault
AL
01
Last but one activated alarm/fault
AL
02
Third from last activated alarm/fault
AL
03
Previous activated alarm/fault
AL
04
Previous activated alarm/fault
AL
05
Previous activated alarm/fault
AL
06
Previous activated alarm/fault
AL
07
Previous activated alarm/fault
AL
08
Previous activated alarm/fault
AL
09
Previous activated alarm/fault
3.6

Checks

3.6.1

Chimney sweeper function

The chimney sweeper function is used by the qualified
maintenance technician to check the mains gas pressure, detect
the combustion parameters and to measure the combustion
efficiency required by legislation in force.
This function lasts 15 minutes and is activated by proceeding
as follows:
– if the panel (2) has not already been removed, remove the
two screws (1), pull the front panel (2) forwards and release it
from the top by lifting it
2
Range
U/M
Step
0.1; from
0.0 to 9.9;
0 .. 99
h x 1000
1; from 10
to 99
0.1; from
0.0 to 9.9;
0 .. 99
h x 1000
1; from 10
to 99
0.1; from
0.0 to 9.9;
0 .. 99
h x 1000
1; from 10
to 99
0 .. 99
x 1
1
0 .. 99
x 1
1
0 .. 99
x 1
1
1 .. 199
months
1
1 .. 199
x 1
1
1
Fig. 32
85