Intended Use; Product Information; Type Key; Technical Data - salmson LRE Serie Instalacion Y Puesta En Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

English
4

Intended use

Purpose
Fields of application
Contraindications
5

Product information

5.1

Type key

5.2

Technical data

LRE/JRE property
Speed range
Nominal diameters DN
Pipe connections
Permissible min./max. fluid temperature
Ambient temperature min./max.
Storage temperature min./max.
Maximum permissible operating pressure
Insulation class
64
Glanded pumps in the LRE series (in-line single) and JRE series (in-line
double) are intended for use as circulation pumps in building services.
They may be used for:
• Hot water heating systems
• Cooling and cold water circulation systems
• Industrial circulation systems
• Heat carrier circuits
The pumps are exclusively intended for installation and operation in
enclosed rooms. Typical installation locations are technical rooms
within the building with other domestic installations. No provision has
been made for direct installation of the device in rooms used for other
purposes (residential and work rooms). The following is not permitted:
• Outdoor installation and operation outdoors
CAUTION! Risk of property damage!
Non-permitted substances in the fluid can destroy the pump.
Abrasive solids (e.g. sand) increase pump wear.
Pumps without an Ex rating are not suitable for use in potentially
explosive areas.
• The intended use includes complying with these instructions.
• Any other use is considered to be outside the intended use.
The type key consists of the following elements:
Example:
LRE 204-16/4-xx
JRE 204-16/4-xx
LR
Flange-end pump as single pump
JR
Flange-end pump as double pump
E
Inline pump with Electronic module for electronic
speed control
2
Number of poles, motor
04
Nominal diameter DN of the flange connection
[mm]
Impeller diameter [mm]
16
4
Rated power P
xx
Variant: e.g. R1 – without differential pressure
sensor
Value
750 – 2900 rpm
32/40/50/65/80 mm
Flanges PN 16
-20 °C to +120 °C
0 to +40 °C
-20 °C to +60 °C
10 bar
F
[kW]
2
Remarks
EN 1092-2
Depending on fluid
Lower or higher ambient
temperatures on request
Salmson 11/2017

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Jre serie