3.4 - GENERAL EXAMPLES OF INSTALLATION
EXAMPLE 1
1. M16/RM N.C. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
6. EVP/NC fast opening automatic
solenoid valve
11
12
1
EXAMPLE 2 (Burner Gas Train)
1. FM gas filter
2. OPSO series MVB/1 MAX shut off valve
3. RG/2MC pressure regulator
4. Minimum pressure switch
5. EVP/NC fast opening automatic
solenoid valve
6. Maximum pressure switch
Madas Technical Manual - REV. 0 of 10
10
2
3
13
12
1
2
May 2018
th
7. Solenoid valve control device
8. MVS/1 relief valve
9. Pressure gauge and relative button
10. Gas detector
11. SM remote jerk ON/OFF valve lever control
12. Expansion joint/anti-vibration mount
9
4
5
7. EVPS/NC slow opening automatic solenoid valve
8. External reset
9. Burner control
10. MTC10 Valve proving system
11. MVS/1 relief valve
12. Pressure gauge and relative button
13. Gas detector
12
3
17
discharge in
open air
8
9
6
discharge in
open air
10
11
4
5
6
7