5. Commissioning, operation
5.3 Fitting a DIN 175301-803 angular connector
1. Loosen the screw (1).
2. Loosen the cable gland (2).
3. Pull the angular connector (5) + (6) away from the instrument.
4.
CAUTION!
Improper mounting
The seal of the angle housing will be damaged.
Do not try to push the terminal block (6) out using the
screw hole (1) or the cable gland (2).
Via the mounting hole (D), lever the terminal block (6) out of the angle
housing (5).
5. Slide the cable through the cable gland (2), the ring (3), the sealing (4) and
the angle housing (5).
6. Connect the cable ends to the terminal blocks (6) in accordance with the
connection diagram.
7. Press the angle housing (5) onto the terminal block (6).
8. Make sure that the seals are not damaged and that the cable gland and
seals are correctly seated in order to ensure ingress protection.
9. Tighten the cable gland (2) around the cable.
10. Place the flat gasket (7) over the instrument's connection pins.
11. Push the angular connector (5) + (6) onto the instrument.
12. Tighten the screw (1).
WIKA operating instructions pressure transmitter, model A-10
(D)
(2)
(3)
(4)
(1)
(5)
(6)
(7)
(8)
11