AERMEC VMF-RCC Manual Del Usuario página 112

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Document
E5 panel technical specifications
Edition
1
Date
Terminal
M9
M10.AI3 ÷ M10.AI4
M10.AI5
M10.AI6
M11 (OUT1/2/3)
M11 (+24V)
M12
M5
M6
M7
M8
M2 (O1, O2, O3,
O4, O5, O6)
M4 (O10, O11, O12) Triac outputs
M3 (O7, O8)
M3 (O9)
M1
112
2104_2696105_00
09/08/2017
Author
Description
NTC probe input
NTC probe input
Analog input 4÷20 mA
Analog input 0÷10 V
Analog outputs 0÷10 V/ PWM
Auxiliary voltage
Digital inputs
Digital inputs
Digital inputs
RS485 serial port
(for connection to bus)
RS485 serial port
(not used)
Triac outputs
Triac outputs
Clean contact output from relay
Board power supply input
Table 1: electric features of VMF-REB expansions
Communication
cable braid
Figure 5: serial connection to VMF-REB expansions
F. Carpanese
Electric features
R(25°C) = 10Kohm, B(25°/50°C)= 950K
R(25°C) = 10Kohm, B(25°/50°C)= 950K
I max 20 [mA]
V max 10 [V]
V max 12 [V] / I max 2 [mA]
V 24[V] / I max 125 [mA]
V max 12 [V] / I max 10 [mA]
V max 12 [V] / I max 10 [mA]
V max 12 [V] / I max 10 [mA]
V max −9 [V] ÷ +14 [V]
V max −9 [V] ÷ +14 [V]
V max 230 [V]/ I max 100 [mA]
V max 230 [V]/ I max 0.7 [A]
V max 230 [V]/ I max 100 [mA]
V max 250 [V]/ I max 6 [A]
V max 230 [V]/ I max 5 [A]
Code
Type
indoor

Publicidad

Tabla de contenido
loading