AERMEC VMF-RCC Manual Del Usuario página 82

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Regulation and Control Service
Project
VMF-RCC panel
Electronic adjustment
Subject
Document
E5 panel technical specifications
Edition
1
Date
Using the copy key, enable and/or disable the SET BLOCK at all fan coils.
N.B.: The
/
The
icon indicates that the fan coil system (not the individual!!!!) is momentarily enabled.
Pressing the button disables the functioning of the same and the changing of the image into
.
The
icon indicates that the fan coil system is momentarily disabled. Pressing the button
enables the functioning of the same and the changing of the image into
By pressing the SET key, access the pages regarding the "set fan coils" parameters.
S
ET TEMPERATURE PAGE
From this page it is possible to read and/or modify the regulation set at which the fan coil
thermostats are forced to work. The range of acceptable values is 0 ÷ 33.0 [°C].
enable/disable the set
point forcing by the
If the SetPoint is:
• LOCKED = the setpoint cannot be edited from the terminal on the machine (VMF-E2 or E4);
• UNLOCKED = the setpoint can be edited from the terminal on the machine (VMF-E2 or E4);
If the Mode is:
82
2104_2696105_00
File
09/08/2017
Author
key is active if the fan coils work with the set block.
Key to
supervisor
SpecificheTecnicheVMF_RCC(Ed0)_EN.doc
F. Carpanese
Page 30/61
Code
Group
Code
Type
indoor
.
Keys to select the forced
functioning mode of the
zone.

Publicidad

Tabla de contenido
loading

Tabla de contenido