Regulation and Control Service
Project
VMF-RCC panel
Subject
Electronic adjustment
E5 panel technical specifications
Document
Edition
1
Date
 Use this`page to enable (DHW) or disable (NO DHW) DHW in the system. Level:
super_user.
 Use this page to edit the chiller water output set for DHW production. The acceptable
values range from 30.0 to 70.0 [°C]. Level: super_user.
This is a read-only parameter
To enter the data editing mode, press the
displayed. To change the value, act on the increase (
confirmed by pressing the enter (
highlighted by the disappearance of the denied display.
Press the ESC key for the system to display the menu page.
Using the Page Up and Page Down keys, scroll the pages contained in the sub-menu.
RAS
PAGE
Use this page to:
 enable (ON) or disable (OFF) the contemporaneity of system loads. Level: super_user.
 set the switch-on delay parameter of the integration resistance inside the storage tank.
The values accepted range from 0 to 60 [min]. Level: super_user.
File
09/08/2017
Author
if "Control type" is set as modu_control.
) key, while the effective memorisation in eeprom is
SpecificheTecnicheVMF_RCC(Ed0)_EN.doc
F. Carpanese
key. This status is highlighted if no string is
) and decrease (
Page 37/61
Code
Group
Code
Type
indoor
) keys. The data is
2104_2696105_00
89