3G4000W outputs

The 3G4000W can use two programmable outputs to activate in response to the associated events.
For more information, see the

Activating the outputs

About this task: The 3G4000W has two open collector outputs capable of a maximum of 50 mA.
Internal events on the 3G4000W can trigger the output to turn on an LED or activate an input on the
host panel. You can also configure the outputs to activate for a programmable duration.
1.
Connect a programmable output to the control panel as
2.
Define the control panel input zone or point as 24 hr Supervisory with a keypad-only
notification when activated. Local keypads sound when the 3G4000W detects a trouble
condition.

Output 1

Output 1 is normally low and switches to high when the system detects one of the following
conditions:
• Wireless network trouble
• Failure to communicate trouble (FTC)
• Insufficient signal strenght or radio
• SIM trouble
The output switches back to low when all the trouble conditions are restored.

Output 2

By default Output 2 is not active. The system uses Output 2 for general use and you can configure it
to activate for a number of trouble conditions.

Reporting codes

The following table displays the reporting codes for the 3G4000W.
Table 8: Reporting codes
Reporting code
PSTN Line Down
PSTN Line Restoral
Input Power Loss
Input Power Loss
Restoral
Low Battery Trouble
Low Battery Restoral
3G4000W 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL 5.0
3G4000W wiring diagram (Figure
Contact ID
E351-000
R251-000
E337-000
R337-000
E338-000
R338-000
2).
Figure 4
illustrates.
SIA
LT-000
LR-000
YP-000
YQ-000
YT-000
YR-000
Notes
Telco fault
Telco fault restore
Power supply trouble
Power supply trouble
restore
Communicator battery
trouble
Commuicator battery
trouble restore
17