This status indicates the name of the cellular radio model. The 3G4000W communicator indicates
UE910-GL in this field.
[913] – Radio Firmware Version:
This status indicates the current firmware version of the cellular radio module.
[915] – Tower ID:
This status indicates a 7 digit hexadecimal ID that can be used to locate the cellular tower, or cell ID,
that the radio is currently attached to. This may be used for troubleshooting purposes.
[918] – PTM Count:
This status shows the current panel transmission monitoring error count. This feature is only active
when the 3G4000W is configured as a backup communicator.
[921] – Battery Voltage:
This status shows the voltage measured from the battery the last time it was tested. The nominal
battery voltage is 7.2V.

Zones tab

Use the two onboard zone inputs to monitor various functions. Each zone has its own set of
configurable options. Typically, the zone inputs are wired to programmable outputs from the
security panel to allow central station communication of various states and trouble conditions using
the cellular channel.
Zone Definitions: There are 5 zone definitions that are available for selection. Reporting code
identifiers denote which zone input has been tripped when delayed 24 hour fire, 24 hour panic, 24
hour burglary, system trouble or AC power trouble are defined as zone types. Contact ID events
may include an identifier of 991 for zone 1 and 992 for zone 2. SIA events may include an identifier
of 001 for zone 1 and 002 for zone 2.
Table 11: Zone definitions and reporting codes
Zone Type Definition
01
02
03
04
13
Alarm / Alarm Restore Options: These settings determine whether the communicator sends
alarm or alarm restore reporting codes when the zone changes state. In some cases it may be
desirable to only communicate the alarm conditions but not the restore conditions.
Alarm / Restore Contact ID Reporting Code: This option is dependent on whether SIA or Contact
ID has been selected for the communicator's reporting format. If Contact ID is selected, the
reporting code used for the zone alarm and restore condition can be modified using this entry.
Zones use default reporting codes, so this entry doesn't typically need to be programmed.
Alarm SIA Reporting Code: This option is dependent on whether SIA or Contact ID has been
selected for the communicator's reporting format. If SIA is selected, the reporting code used for the
zone alarm condition can be modified using this entry. Zones use default reporting codes, so this
entry doesn't typically need to be programmed.
3G4000W 3G (HSPA) WIRELESS ALARM COMMUNICATOR INSTALLATION MANUAL 5.0
Zone Type
Delayed 24 Hour Fire
24 Hour Panic
24 Hour Burglary
System Trouble
AC Power Trouble
Reporting Codes
Contact ID: E11A / R11A SIA: FA / FH
Contact ID: E11A / R11A SIA: FA / FH
Contact ID: E13A / R13A SIA: BA / BH
Contact ID: E13A / R13A SIA: BA / BH
Contact ID: E13A / R13A SIA: BA / BH