7.3

Opening the burner

Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
 Remove screw 1) and take out cover 2)(Fig. 40).
 Disengage the articulated coupling 3) from the graduated
sector 4)(Fig. 40).
 Remove the screw 5) and split pin 9) and pull back the
burner on the guides 6)(Fig. 40) by about 100 mm.
Disconnect the cables of the probe and electrode, then pull
the burner back completely.
 Turn it as indicated in the diagram, and insert the split pin 9)
into the hole of one of the two guides so that the burner
remains in that position.
Now extract the gas distributor 7) after having removed the screw
8)(Fig. 40).
7.4

Closing the burner

 Remove the split pin 9)(Fig. 40) and push the burner until it
is approx. 100 mm from the pipe coupling.
 Reconnect the cables and slide in the burner until it comes
to a stop.
 Reposition the screw 5) and split pin 9)(Fig. 40) and carefully
pull the probe and electrode cables outwards until they are
slightly taut;
 Re-couple the articulated coupling 3) to the graduated sec-
tor 4)(Fig. 40).
Carry out all maintenance work and mount the
casing again.
Maintenance
31
GB
D535
Fig. 40
20040559