ELECTRODE / IONISATION PROBE ADJUSTMENT DIAGRAM
1- Diffuser
2- Internal diffuser
3- Flame disk
4 - Ignition electrodes
5- Nozzles
6- Nozzle holder

AIR/FUEL ADJUSTMENT SERVOMOTOR

CAM REGULATION ON SERVOMOTOR SQN 30.401
1 On/Off lever for motor-camshaft
coupling.
2 Reference Index
3 - Position indicator
I
Adjustment cam for maximum air opening (130°)
II Total air closure (burner off) (0°)
III Adjustment cam for minimum air opening (30°)
IV Adjustment cam for diesel oil 1
V Cam for the activation of 2nd flame diesel oil valve (greater than cam IV) (70°)
To modify the adjustment of the 3 cams used, use the respective red rings (I - II
- III....). The index on the red ring indicates on the respective reference scale the
rotation angle set for each cam.
After installing the nozzles, check the correct position of the electrodes and disk
according to the following measurements indicated in mm.
It's advisable to check levels after every intervention on head.
RECOMMENDED NOZZLES:
TBML 80 MC
TBML 120 MC
TBML 160 MC
TBML 200 MC
1
3
flame (50°)
st
25 / 34
0006081545_201305
STEINEN type SS 45° (TBML 80 MC - 120 MC - 200MC)
MONARCH type HV 45° (TBML 160 MC)
A
B
1 ÷ 1,5
20 ÷ 21
6 ÷ 7
1 ÷ 1,5
20 ÷ 21
6 ÷ 7
1 ÷ 1,5
20 ÷ 21
6 ÷ 7
1 ÷ 1,5
20 ÷ 21
7 ÷ 8
ADJUSTABLE CAM
2
C
D
E
3 ÷ 4
5 ÷ 6
3 ÷ 4
8 ÷ 9
3 ÷ 4
8 ÷ 9
3 ÷ 4
8 ÷ 9