TECHNICAL SPECIFICATIONS

THERMIC POWER
NOx EMMISION
OPERATION
THERMIC POWER
NOx EMMISION
MAXIMUM FUEL VISCOSITY
OPERATION
IGNITION TRANSFORMER
FAN MOTOR
ABSORBED ELECTRICAL POWER*
LINE FUSE
VOLTAGE
PROTECTION RATING
FLAME DETECTOR
NOISE **
WEIGHT
*)
Total absorption at start with ignition transformer on.
**) Noise levels measured in the laboratory of the manufacturer, with burner running on test boiler, at maximum nominal thermal output.
BURNER/BOILER FIXING FLANGE
INSULATING SEAL
STUD BOLTS
NUTS
FLAT WASHERS
FIBREGLASS ROPE
HOSES
DIESEL FILTER
NIPPLE
TBML 80 MC
850
MAX kW
180
MIN kW
< 80 mg/kWh (Class III according to EN 676)
Two-stage progressive / modulating burner
850
MAX kW
350
MIN kW
< 185 mg/kWh (Class II according to EN 267)
1.1 - 2800 r.p.m. 1.5 - 2800 r.p.m.
kW
1.50
kW
6
A / 400 V
78
dBA
90
kg
TBML 80 MC
No. 2 - 1/2"x3/8"
5 / 34
0006081545_201305
TBML 120 MC
TBML 160 MC
1200
1600
250
350
1200
1600
450
550
5.5 cst/20° C - 1.5° E / 20° C
Two-stage
26 kV - 48 mA - 230 V/ 50 Hz
1.90
10
3N ~ 400 V ±10%- 50Hz
IP 40
UV PHOTOCELL
76
98
TBML 120 MC
TBML 160 MC
1
1
No. 4 M 12
No. 4 M 12
No. 4 Ø 12
No 1
No. 2 - 1/2"x3/2"
3/8"
No. 2 - 1/2"x3/8"
TBML 200 MC
2000
450
< 120 mg/kWh (Class
II according to EN
676)
2000
700
3 - 2800 r.p.m.
3.40
16
83
98
TBML 200 MC