12

PLC settings

WARNING!
To avoid unintentional start of the vacuum unit, the pilot signal fuse F6 in terminal no 3
must be removed during settings are made.
The main switch must be ON. The maintenance switch must also be ON, otherwise an
error message will appear. Use arrows
keeping arrow pressed. Settings can be made in menu 1 and menus 4–11.
Options not installed in the plant, but always prepared for in the starter,
can be ignored. Detailed information about all settings are found in
Chapter '12.1 PLC Settings, detailed instructions'.
SIEMENS
TD 200
(Press On/Standby)
0
SHIFT
Press
SIEMENS
TD 200
xxxxh of 2000 h
Trip
1
SHIFT
Press
(2X)
SIEMENS
TD 200
x xxx (x10) h
total
2
SHIFT
Press
(3X)
SIEMENS
TD 200
Software version
2001- 01-04
3
SHIFT
Press
(4X)
SIEMENS
TD 200
Filter cleaning
Ton=4 s Toff=120 m
4
SHIFT
Press
(5X)
SIEMENS
TD 200
Stop delay (SSR) 30 m
5
SHIFT
Starting point
The installation is at standstill with displayed information as per
illustration. By pushing "Esc" the program returns to this point
without saving the last entered setting (Does not apply to Week
ESC
ENTER
Timer Menu.) If the display is left inactive for 30 s it automatically
returns to this point.
Service hour meter, "trip meter"
The display is a trip meter showing running hours from preceding
service as well as the chosen service interval.
Press
to change interval
ENTER
ESC
ENTER
to confirm and automatically return to 0
Press
ENTER
Service hour meter, total running hours
The display shows total running hours.
Max display 99990 h (9999x10).
No settings possible.
ESC
ENTER
Software version
No settings possible. Extended/new software can be ordered and
installed using EPROM.
ESC
ENTER
Filter cleaning
Press
to select T
ENTER
Press
to confirm T
ENTER
ESC
ENTER
and select T
off
Press
to confirm T
ENTER
Automatic start/stop
Press
to select SSR
ENTER
ESC
ENTER
to confirm SSR and return to 0
Press
ENTER
High Vacuum Starter, Advanced
to switch between menus. " Fast wind" by
Increase
Decrease
Increase T
Decrease T
on
Increase T
Decrease T
on
and return to 0
off
Increase time
Decrease time
EN
(Default =
2000 h)
(Default =
on
4 s)
on
(Default =
off
120 min)
off
(Default=30 min,
suitable for
VAC-units.
For RBU-units
10 min is recom-
mended)
19