Specifications
The recommended calibration interval is one year.
General
Display: LCD
Noise: ≤ 1 LSD at frequencies less than 10 Hz
Normal Mode Rejection Ratio: 50 dB at 50/60 Hz
Temperature Effect: ±0.01% / °C based on 23 ° ±25 °C
Warm-up Time: 10 seconds to specified accuracy, 2 minutes to maximum accuracy
Automatic Power-off: 30 minutes
Operating Conditions: –20 to 55 °C (–5 to 130 °F), 10% to 80%, relative humidity, non-condensing
Storage Conditions: –25 to 55 °C (–13 to 130 °F), 10% to 70%, relative humidity, non-condensing
Remove batteries
Batteries: Six AA 1.5-Volt Batteries (NEDA 15A or IEC LR6) Alkaline recommended
Battery Life
Milliamp Source and 2-wire Modes: Nominal 50 hours at 12 mA, 20 hours at 20 mA with
250 ohm load
Other Functions: Nominal 50 hours
Low Battery Indication: BAT indicator appears on the LCD at approximately 4 hours remaining
Fuses: Three 63 mA, 250 V F, 5 x 20 mm
Milliamp - Source and 2-Wire Transmitters - Power & Measure
Ranges: 0.00 mA to 24 mA; –25.0 to 125.0% of 4 mA to 20 mA
Accuracy: ±0.02 mA
Typical Drive Capability: 1200 ohms at 20.00 mA
Compliance Voltage: Nominal 25 V at 20 mA
2-Wire Transmitter Simulator
Ranges: 1.00 mA to 24 mA; –18.0 to 125.0% of 4 mA to 20 mA
Accuracy: ±0.02 mA
Loop Voltage Limits: Minimum, 3 VDC; Maximum 45 VDC
Overload Protection: Current limited to 25 mA nominal
All manuals and user guides at all-guides.com
IPM-300
33