User Manual
INGECON® SUN LITE
AAY2000IKE01
3.10
Change Inv. number
This menu is used to assign a number to the inverter. This is necessary during the configuration of the communications.
Use the up and down keys
Click on OK to confirm the nº selected.
12:00
MAIN MENU
Change date
Start / Stop
Partial Data Reset
Change inv number
3.11
Autotest
Some equipment configurations feature an addition self-test sub-menu
called AUTOTEST. In these configurations, this sub-menu will appear at
the end of the main menu.
To access this menu click on OK over AUTOTEST.
Once in this menu, the voltage and frequency protections are self-
tested by changing the threshold limit values and checking for correct
disconnection.
To perform this test, use keys
test function START AUTOTEST or the results function RESULTS. The
progress of the AUTOTEST algorithm is shown on the bottom of the
screen. The different statuses are as follows:
Status: Stop. There is no AUTOTEST in progress.
Status: Start An AUTOTEST process is starting.
Status: Vmax. The upper threshold limit of the voltage protection is
being tested. The voltage protection value is shown, which is gradually
changed by the algorithm until disconnection is verified.
Status: Reconnexion Each time a Vmax, Vmin, Fmax or Fmin status is
completed, the connection status appears to indicate that the following
AUTOTEST measurement is starting.
Status: Vmin. The lower threshold limit of the voltage protection is being tested.
Status:Fmax. The upper threshold limit of the frequency protection is being tested.
Status:Fmin. The lower threshold limit of the frequency protection is being tested
Status: Complete. When the AUTOTEST has been completed.
The AUTOTEST can be interrupted at any time by selecting the end self-test option STOP AUTOTEST, which appears in place of
the start self-test prompt START AUTOTEST, whilst the test is in progress.
Once a self-test has been completed, the results can be viewed by
selecting RESULTS. Click on OK to access the results, and you
can then move between the four screens displaying the results
available. As an example, shown below are the results screens
for Vmax and Fmax.
12:00
AUTOTEST
Results Vmax
Vmax ;
238 V
Vac ;
236 V
Time: 070 ms
AAY2000IKE01
Rev. _
Date: MArch 2011
and
respectively, to change the inverter number.
12/04/10
and
to access the start self-
12/04/10
12:00
CHANGE INV NUMBER
Inverter number 101
Confirm (OK)
Cancel (ESC)
12:00
MAIN MENU
Start / Stop
Partial Data Reset
Change inv number
Autotest
12:00
AUTOTEST
Start Autotest
Results
Status: Start
12:00
AUTOTEST
Stop Autotest
Results
Status: Vmax
12:00
AUTOTEST
Results Fmax
Fmax ;
50.02 Hz
Fac ;
49.99 Hz
Time: 060 ms
09/01/09
12/04/10
12/04/10
12/04/10
12/04/10
Page 21 of 68