Ingeteam
18.18. Place the inverter in operating mode
To start the inverter in operating mode, open MAIN MENU > START/STOP. This screen displays the inverter's
current status and allows changing the status using the OK key. If the current status is stopped, press OK to
change it to operational.
18.19. Place the inverter in stop mode
To start the inverter in stopped mode, open MAIN MENU > START/STOP. This screen displays the inverter's current
status and allows changing the status using the OK key. If the current status is operating, press OK to change it to
stopped.
18.20. Change date and time
To change the inverter's date and time, open MAIN MENU > CONFIGURATION > CHANGE TIME/DATE.
18.21. Change display language
To change the display language, open MAIN MENU > LANGUAGE
18.22. Viewing alarms and stop reasons
During the operation of the unit, alarms and stop reasons may be generated.
To view the alarms in real time, open MAIN MENU > MONITORING > ALARM MONIT.
In addition to alarms, various unit operation codes can be viewed on this display. These codes provide information
next to the alarm in order to solve the problem.
18.23. Performing an emergency charge of the battery
An emergency charge must be performed when the installation is stopped due to a total battery discharge.
This function allows to charge the batteries up to a certain level in order to have enough energy to restore the
system again.
For the unit to carry out an emergency charge, the batteries must be in one of the following states:
•
Low charge level, SOC <= SOCdescx. (Alarm 0x0001 + Code2 0x0080)
•
Low voltage, Vbat <= Vmin. (Alarm 0x0001 + Code2 0x0080)
The inverters can charge the batteries from different energy sources. Depending on the energy source available,
this emergency charge will be automatically activated by the inverter or must be activated manually by the user.
Available energy source
Photovoltaic input in the
INGECON SUN STORAGE 1Play
Auxiliary grid/genset
68
Emergency charge
Automatic
Automatic
Description
The inverter detects the PV array and automatically
starts charging the batteries.
The installation will be restored when the batteries reach
the configured SOCrecx state of charge (see "18.8.
Configuring the operation mode and its settings").
The inverter detects the voltage and frequency in the AC
grid input and connects to it automatically.
The installation is restored immediately and starts
charging the batteries from the AC grid input (see
"18.9. Configuring the maximum battery charge
power from the auxiliary grid/genset").
ABH2013IQM01_C- Installation and Operation Manual
Display control