Installation Instructions

1 General information

The meter has left the factory in a technically safe condition.
Further technical support is provided by the manufacturer on
request. The meter's calibration-relevant security symbols
must not be damaged or removed. Otherwise, the warranty
and calibration validity of the meter will be invalidated.
Keep the packaging in a safe place so that you can
transport the meter in its original packaging after the
calibration validity has expired.
Lay all cables at a minimum distance of 500 mm from
power and high-frequency cables.
A relative humidity of < 93 % at 25°C is permissible
(non-condensing).
Avoid overpressure cavitation throughout the system,
i.e. at least 1 bar for qp and approx. 3 bar for qs
(applies for approx. 80 °C).
The control line must not be cut, shortened or
extended.
In the case of a heat meter or combined heat/cooling
meter, the cold side installation location
corresponds to the return
installation location corresponds to the supply
In the case of a cooling meter
installation location corresponds to the return
the cold side installation location to the supply

2 Safety instructions

Caution
The meters may only be used in building installations
and only for the applications described.
Caution
The meter is designed in accordance with the
guidelines for environmental classes M2+E1 and must
be installed in accordance with these regulations. The
local regulations (installation, etc.) must be observed.
Caution
The operating conditions on the nameplate must be
observed during use. Failure to comply with these
regulations can cause dangerous situations and voids
all claims arising from liability for defects as well as
liability on the basis of any expressly granted
guarantees.
Caution
Comply with the requirements for circulation water
(CEN / TR 16911:2016).
Siemens Smart Infrastructure
Ultraschall-Wärme- und Kältezähler
WSx8
and the warm side
.
, the warm side
and
.
A6V11905994
Caution
The meter is only suitable for circulation water in
heating systems.
Caution
The meter is not suitable for drinking water.
Caution
Do not lift the metre on the calculator.
Caution
Pay attention to sharp edges on threads, flanges and
the measuring tube.
Caution
Only personnel trained in the installation and operation
of meters in heating/cooling systems may install and
remove the meter.
Caution
Only install or remove the meter on an unpressurised
system.
Caution
After installing the meter, check the leak tightness of
the system.
Caution
Breaking the safety marks relevant for calibration
voids the warranty and the validity of the calibration.
Caution
Avoid contact of the meter housing with silicone oils or
substances containing silicone oil.
Caution
Only clean the meter from the outside with a soft,
slightly moistened cloth. Do not use spirits or cleaning
agents.
Warning
The meter must not be energised until it has been fully
assembled. Otherwise there is a risk of electric shock
on the terminals. A defective or obviously damaged
device must be disconnected from the power supply
immediately and replaced.
A6V11905994
14.01.2020
Translation
WSx8
14.01.2020
9