K.M080.. / K.M100H.. / K.M150L.. / K.W080.. / K.W100L.. / K.T040H.. / K.D200N..+0075..
DIAGRAM FOR ELECTRIC PUMP CABLE CONNECTIONS
GB
L1 (u)
L1 (R)
POWER
L2 (v)
L2 (S)
SUPPLY LINE
L3 (w)
L3 (T)
It is OBLIGATORY to connect thermal probes for flameproof electric pumps (series - ...X...) (see section 20.1).
POWER CABLE DIAGRAM
Electric pump with a 7-conductor cable
(no. 3 for power supply + no. 4 auxiliary conductors): direct start;
power supply voltage corresponding to the electric pump voltage reported on the
plate
U1
V1
W1
Panel connection
For codes with motor power supply voltage 1 and 4
(see electric pump ID)
19. GROUND CONDUCTOR CONNECTIONS
The Yellow/Green ground terminal in the electric pump cable must be connected to the grounding circuit of the system
before the other terminals are connected. Furthermore, it must be the last terminal to be disconnected if the electric pump
is disconnected.
For electric pumps in flameproof version, an additional external ground terminal located in the cable input area is required.
Connection of this terminal with the grounding circuit of the system is at the installer's charge.
26
L1 (R)
L2 (S)
L3 (T)
CONDUCTIVITY
DETECTOR
COIL
Electric pump with a 10-conductor cable
(no. 6 for power supply + no. 4 auxiliary conductors):
Direct start - connection to ∆
electric pump with plate 230V∆, grid voltage 230V
electric pump with plate 400V∆, grid voltage 400V
U1
W2
V1
U2
W1
V2
Panel connection
For codes with motor power supply voltage 2 and 3
(see electric pump ID)
G/V
S
T1
T2
L1 (R)
L2 (S)
L3 (T)
Caprari S.p.A.