General Settings; Automatic / Manual Mode - Lowara SM30 BSETF3 Instrucciones Para La Instalación Y El Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 140

5 GENERAL SETTINGS

CAUTION

5.1 Automatic / manual mode

When switched on the electronic board is set in automatic mode.
In the case of a system with a pressure sensor, this window appears:
##.## is the current pressure value.
In the case of a system with pressure switches, this window appears
It is possible to pass from AUTOMATIC to MANUAL mode, and vice versa, by pressing the ↑UP button.
In MANUAL and AUTOMATIC mode the Alarms Log can be displayed by pressing the ↑UP and OK/MENU
buttons simultaneously. The following window appears
From AUTOMATIC mode (if enabled in the System Menu) or MANUAL mode, the parameters setting
menu can be accessed by pressing the ↓DOWN and OK/MENU buttons simultaneously.
5.2 General rules for modifying and inserting data
In a menu, use the ↑UP and ↓DOWN buttons to move from one window to another. Each window refers
to a single parameter to be set or to a submenu.
For each window a default value is proposed which may be modified as required.
To modify a parameter or access a submenu, in a window, press the OK/MENU button.
The adjustments may influence correct operation of the set.
AI1 + ###.## bar
AUT: PRESSURE SW
------------
ALARMS
AUTO
LOG
en
37