Technical Data; Performance Data; Function; Functional Description - oventrop TRV9 Manual De Instrucciones

Ocultar thumbs Ver también para TRV9:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.2 Storage
The thermostatic valve set must only be
stored under the following conditions:
• Do not store in open air, keep dry and
free from dust.
• Dot not expose to aggressive fluids or
heat sources.
• Protect
from
mechanical agitation.
• Storage temperature: –20°C up to +60°C
• Max. relative humidity of air: 95 %
3.3 Packaging
Packaging material is to be disposed of in
an environmentally friendly manner.

4 Technical data

4.1 Performance data

Operating temperature t
Max. operating
pressure p
:
s
Fluid:
Recommended
differential pressure:
Max. differential
pressure:
Dimensions:
Thermostatic valve according to EN215,
series D
"Combi 2" according to DIN 3842
12
direct
sunlight
and
: 2°C up to 120°C
s
(for short periods up
to 130°C)
10 bar
Water or suitable
mixtures
of
eth-
y l e n e / p r o p y l e n e
glycol and water
according to VDI
2035
/
ÖNORM
5195 (max. glycol
proportion 50 %, ph
value 6.5-10). Not
suitable for steam
or oily, polluted and
aggressive fluids.
30 – 200 mbar
1 bar
!
DANGER
Suitable measures, e.g. safety valves,
have to be taken to ensure that the max.
operating pressures and max. and min.
operating temperatures are not exceeded
or undercut.

5 Function

5.1 Functional description

The thermostatic valve "AV 9" is fitted with
an infinitely presettable valve insert and
allows for a trouble-free, exact adaptation of
the flow rates to the required heat demand.
The radiator lockshield valve "Combi 2"
with proportional fine setting and isolating
facility allows for the removal of the radiator
without draining the system.
Hydronic balancing of the heating system
can be carried out with the help of the
presetting of the thermostatic valve or the
radiator lockshield valve.
This way, a constant warming up of all
radiators in a heating system is guaranteed.
Note:
To avoid increased differential pressures at
the thermostatic valves and disturbing flow
noises, installation of automatic differential
pressure
regulators
circulation pumps in the central supply
risers is recommended.
The thermostat "vindo TH" together with
the thermostatic valve is a proportional
controller working without auxiliary energy.
It regulates the room temperature by varying
the volume flow of the heating water.
and
controlled

Publicidad