6.2.3 Setting of the radiator lockshield
valve
1. Remove the protection cap.
2. Close the valve disc by turning a
6 mm spanner (1) to the right (illustr. 3).
Illustr. 3 Isolation of the radiator lockshield
valve
3. Now set the valve disc by turning the 6
mm spanner (1) anticlockwise according
to the number of turns selected from the
flow chart (illustr. 4)
Illustr.4 Setting of the radiator lockshield
valve
6.2.4 Isolation of the radiator lockshield
valve
1. Remove the protection cap.
2. Close the valve disc by turning a
6 mm spanner (1) to the right (illustr. 3).
6.3 Installation of the thermostat
NOTICE
Do not fit the thermostat until all building
work has been completed to avoid
damage to the thermostat.
closing
setting
1. Set the thermostat to position "5".
2. Align the thermostat so that the
indicator mark is clearly visible.
3. Hold in this position and tighten the
collar nut (do not use excessive force).
Set the thermostat to the required room
temperature (illustr. 5).
NOTICE
Do not use excessive force during
thermostat installation to avoid damage
to the thermostat and thread.
approx. 28ºC / 82ºF
approx. 24ºC / 75ºF
approx. 20ºC / 68ºF
approx. 16ºC / 61ºF
approx. 12ºC / 54ºF
approx. 7ºC / 45ºF
Illustr. 5 Temperature scale thermostat "vindo
TH"
6.3.1 Limitation and locking of the
thermostat
The control range of the thermostat can
be limited or locked to any graduation line,
figure of the frost protection symbol with the
help of the limiting clips which can be found
inside the handwheel.
15