If the separate receiver unit is installed on the ceil-
ing, use the provided ceiling mounting bracket for
installation.
1. Insert a screwdriver or similar tool into the notch at
the bottom to remove the receiver nameplate.
GB
2. Cut a section out of the ceiling along the provided
paper pattern (95 × 51 mm).
3. Pass the wire through the provided mounting
bracket and insert the bracket into the installation
FR
hole. (Fig. 11-17)
4. Use bracket parts (A) and (B) to securely grip the
ceiling material. (Fig. 11-18)
DE
5. Connect the receiver wire (2-core) to the wire from
the indoor unit.
(Refer to "Wiring the Receiver Unit".)
Check the terminal number on the indoor unit
IT
before wiring the receiver unit and be sure not to
wire incorrectly. (The unit will be damaged if high
voltage, such as 200 V AC, is applied.)
6. Adjust the provided spacers so that they are
PT
several millimeters larger than the thickness of the
ceiling material. Pass the 2 supplied screws (M4 ×
40) through the spacers and tighten them enough
to hold the receiver unit in place.
GR
7. Return parts (A) and (B) through the gap between
the ceiling and receiver unit so that they are
contained in the openings. Then tighten the
screws. Do not tighten the screws excessively. This
ES
may result in damage or deformation of the case.
Tighten to the point where the receiver unit can be
moved slightly by hand. (Fig. 11-19)
8. Reattach the nameplate.
DC̲Inverter̲Eng.indd 112
DC̲Inverter̲Eng.indd 112
Fig. 11-17
Fig. 11-18
Fig. 11-19
112
Part (A)
Part (B)
2007/07/25 13:21:56
2007/07/25 13:21:56