Taping The Tubes; Finishing The Installation - Sanyo SPWXDR124GH56A Manual Del Usuario

Tabla de contenido

Publicidad

7-4. Taping the Tubes

(1) At this time, the refrigerant tubes (and electri-
cal wiring if local codes permit) should be taped
together with armoring tape in 1 bundle. To pre-
vent condensation from overflowing the drain
GB
pan, keep the drain hose separate from the refrig-
erant tubing.
(2) Wrap the armoring tape from the bottom of the
FR
outdoor unit to the top of the tubing where it
enters the wall. As you wrap the tubing, overlap
half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1
DE
clamp approx. each meter. (Fig. 7-12)
NOTE
Do not wind the armoring tape too tightly since this
IT
will decrease the heat insulation effect. Also ensure
that the condensation drain hose splits away from the
bundle and drips clear of the unit and the tubing.

7-5. Finishing the Installation

PT
After finishing insulating and taping over the tubing,
use sealing putty to seal off the hole in the wall to pre-
vent rain and draft from entering. (Fig. 7-13)
GR
ES
DC̲Inverter̲Eng.indd 58
DC̲Inverter̲Eng.indd 58
Inter-unit
control wiring
Fig. 7-12
Apply putty here
Fig. 7-13
58
Gas tube
Liquid tube
Armoring tape
Insulation
Tubing
2007/07/25 13:21:46
2007/07/25 13:21:46

Publicidad

Tabla de contenido
loading

Tabla de contenido