10-8-5. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure
that the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control
PCB, and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an
GB
easily visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1, 2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
FR
* Use the remote controller to check the addresses of the indoor units. Press and hold the
button for 4 seconds or longer (simple settings mode). Then press the
address. (Each time the button is pressed, the address changes as follows: 1-1, 1-2, ... 2-1, 2-2, ....) The
indoor unit fan operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate the
DE
address on the indoor unit.
Press the
button again to return to the normal remote controller mode.
For details, refer to the separate manual.
IT
10-8-6. Main-sub remote controller control
Control using 2 remote controller switches
Main-sub remote controller control refers to the use of 2 remote controllers to control 1 or multiple indoor units.
(A maximum of 2 remote controllers can be connected.)
PT
●
Connecting 2 remote controllers to
control 1 indoor unit
GR
ES
Ground
Ground
(Setting procedure)
(1) Set 1 of the 2 connected remote controllers as the
main remote controller.
(2) On the other remote controller (sub remote
controller), change the remote controller address
connector on the reverse side of the remote
controller switch PCB from the Main position to the
Sub position.
The remote controller will now function as the sub
remote controller.
The sub remote controller will also operate if
connected to indoor unit 2.
DC̲Inverter̲Eng.indd 74
DC̲Inverter̲Eng.indd 74
(Outdoor) 2 - (Indoor) 1, 2...
●
Connecting 2 remote controllers to control a
simultaneous-operation multi system
Remote controller
Remote controller
switch (main)
switch (sub)
Optional
Optional
1 2
1 2
Remote controller wiring
Terminal plate
for remote
1 2
controller wiring
Indoor unit
U1U2
1 2
Outdoor unit
Remote controller
Remote controller
switch (main)
switch (sub)
Optional
Optional
1 2
1 2
Terminal plate
for remote
controller wiring
1 2
1 2
Indoor unit 1
Indoor unit 2
U1U2
U1U2
Ground
Ground
1 2
Inter-unit
Outdoor unit
control wiring
Ground
To Service Technicians
To display the sensor temperature:
To display the trouble history:
Press both
and
buttons on the
Press both
remote controller for more than 4 seconds
remote controller for more than 4 seconds
together.
together.
Change the sensor address (CODE NO.)
Change the alarm message:
with
/
(SET TEMP) buttons.
Select the UNIT NO. that you want to call
CODE NO.
with
button.
Press the
button to finish service mode.
Press the
mode.
RCU.Main
RCU.CK
RCU.Sub
RCU
RCU.ADR
TMNL.
To avoid an electric shock hazard,
WA R N I N G
DO NOT touch any ter-
minal on the Printed Cir-
cuit Board with a metal rod, a
screwdriver edge or bare hand
when power
is supplied.
74
button and
button and select the indoor
Remote controller
crossover wiring
Terminal plate
for remote
controller wiring
1 2
Indoor unit 3
U1U2
Ground
TIMER
TMNL.
and
buttons on the
Remote controller
address connector
/
(SET TEMP) buttons
(New) (Old)
button to finish service
Remote Controller (Main)
Checking remote controller
Changing method for room
temperature sensor (from Indoor
Remote Controller (Sub)
unit to RCU)
1
On the remote controller, press
+
+
at the same time for
more than 4 seconds.
2
Set CODE No.
with
/
(SET TEMP) button.
3
Set DATA from
to
with
/
(TIMER) button.
4
Press
Finally, Press
Fig. 10-8
2007/07/25 13:21:50
2007/07/25 13:21:50