Operation
Allows generating cold air by modulating
the outdoor air intake damper. If conditions
are favourable, the yellow LED V2 will be
on and the damper will adjust to achieve
an impulse temperature of 12° C. Favour-
able conditions in temperature mode are
understood as an outdoor temperature of
General dimensions mm
Economiser
Weight kg
A
VIR 25A
54
729
VIR 40A
69
729
VIR 45A / 60A
78
809
VIR 75A / 90A
90
729
8
below 20° C and, at the same time, below
the return temperature.
The yellow LED on the board will be off when
conditions are not favourable.
Whenever the indoor fan is in operation, the
outdoor damper is open proportionally to
renew the air in the room. (By default, 10%
adjustable value.)
B
C
D
E
566
1 109
408
159
639
1 352
408
159
739
1 935
508
164
812
2 205
508
79
F
G
H
I
162
95
63
205
162
131
100
227
137
101
130
218
142
138
166
228
GB
In winter cycle, if the thermostat calls for
heat but no heat phase can be activated due
to a failure, the outdoor damper will remain
closed with the indoor fan in operation.
Should the indoor fan fail and this is detected
by the Yklon board, the outdoor air damper
closes completely.
J
K
L
M
699
140
130
605
898
212
196
605
1 499
213
112
685
1 724
260
202
605
N
O
40
55
40
55
40
55
40
55