7. Connection with an electric system
Never connect the generator directly to the electricity supply network. In order to use the generator as an automa-
tic auxiliary power source in cases of power failure in an electricity network, contact a qualified electrician. The
generator must be isolated from the electricity network. All applicable laws and regulations must be observed.
ATTENTION:
rator when the network is reestablished causing possible explosion or fire.
WARNING: Inappropriate connections to an electric system might allow the generator to feed the network and
cause electrocution to anyone who has contact with the network during a drop in energy. Consult a capacitated
electrician before connecting a generator to a low voltage network.
MODEL
S1200MG
S2500MG
S3500MG
S5500MG
S8000MG
S12000MG
S5000TD
S13000TD
TABLE 8.1 - INDICATIVE DATA OF COPPER CONDUCTORS AND FUSES FOR MAIN BRANCH.
Improper connections might allow the energy from the network to return to the gene-
START
NETWORK
MODE
VOLTAGE (V)
115
230
115
230
115
230
Direta
115
230
115
230
115
230
220
380
Direta
220
380
CONDUCTOR
CURRENT (A)
(mm²)
1~ Single-Phase
7,4
1,5
3,7
1,5
17,4
2,5
8,7
1,5
24,3
4
12,2
1,5
43,5
10
21,7
4
50
16
25
4
78
25
39
10
3~ Three-Phase
13,1
1,5
7,8
1,5
31,5
10
18,2
2,5
77
DIST. MÁX. (m)
FUSE F1
MÁX. (A)
VOLTAGE DROP (2%)
8
10
33
6
4
25
14
10
6
32
10
16
9
63
15
32
13
63
13
32
13
100
21
50
15
16
45
10
43
50
32
25