hold in position the device that controls the
air flow to the burner head.
N.B.
Check that the ignition occurs in a regular
manner; if the passage between the head
and the disk is closed, it may occur that the
speed of the mixture (combustible air) is
so high that ignition is made difficult. If this
occurs, then the regulator must be opened
gradually until it is in a position where the
ignition occurs in a regular manner, and
this position must be accepted as the set
position. Remember that, for the first flame, it
is preferable to limit the quantity of air to the
bare minimum necessary for a safe ignition,
even in the most demanding cases.
E
N
G
L
I
S
H
AIR / GAS PRINCIPLE DIAGRAM
TO BE SUPPLIED BY INSTALLER
7
Safety gas valve
8
Minimum pressure switch and gas leak control
9
Gas filter
10 Vibration-proof joint (not included in supply)
11 Ball cock (not included in supply)
12 Gas regulation servomotor
AIR REGULATION PRINCIPLE DIAGRAM FOR GAS BURNERS
LIMIT OF BALTUR SUPPLY
0006081047_201109
1
Air regulation servomotor
2
Air pressure switch
3
Maximum gas pressure switch
4
Gas supply control butterfly valve
5
Gas valves for main flame with pressure regulator
6
Valve tightness control device (integrated in the
apparatus)
14 / 18