Attachment points for Rilsan cable ties (not supplied)
2
Recommendation: separate the power cables
3
Attachment points for internal preheating coil static relay
4
Classic cradle fastening point (Classic only)
4.9. Connecting condensates
The water trap connection delivered with the unit must be screwed in by drilling the product's body on the side identified A or B depending on the product
configuration (see point 4.3).
An airflow water trap (membrane or ball) is mandatory. U-bend water traps are strictly prohibited. It is forbidden to glue the connectors together.
Connections must be made with seal connectors as below: (the water trap kit and the elbow are accessories)
5. STARTING/ADJUSTMENTS
5.1. Starting
The product must without fail be configured by one of these two interfaces:
- Aldes InspirAIR
®
remote control
- Aldes Configurator
Refer to the documents on these elements
The unit will not operate if it is not started successfully