The lifting eyebolts of the motor are su-
itable for the weight of the motor. It´s not
allowed to carry the complete pump on
the lifting eyebolts of the motor.
4 Description of product and
accessories
4.1
Description of the pumps
All pumps dealt with herein are single-stage, low-
pressure centrifugal pumps of monoblock design
driven by coupled motor. The mechanical seal is
maintenance-free. The pumps can be installed eit-
her pipe-supported in sufficiently anchored pipe-
work or base-mounted on a plinth.
Its capacity can be infinitely varied if used in con-
junction with the respective control gear (Wilo-CR-
System). This will enable an optimum adaptation of
pump performance to actual load demands and an
economical pump operation.
– IL: The pump housing is of the inline design with
suction and discharge connection axially in line
(Fig.1). All pump housings are designed with the
possibility of base mounting on a plinth. Pumps
with a power 5,5 kW and above to be based
mounted.
– DL: Two pumps heads mounted in a common
housing (double-pump), the pump housing is
being of inline design (Fig. 2). All pump housings
are designed with the possibility of base moun-
ting on a plinth. Pumps with a power 4 kW and
above to be based mounted.
When used in conjunction with an automatic va-
riable speed controller only the base-duty pump
is operated variably. The second pump remains
available for parallel operation to cover peak-
load demand and additionally, for standby duty
to take over under fault conditions.
– BL: Pump with cast iron spiral pump housing and
flangedimensions to DIN EN 733 (Fig.3). Pump
with mounted fixing brace up to motor power 4
kW, 5,5kW and above with foot-mounted motor.
4.2
Scope of supply
IL:
– Single pump
– Installation and operating instructions.
DL:
– Double pump
– Installation and operating instructions.
BL:
– Block end suction pump
– Installation and operating instructions.
4.3
Accessories
Accessories must be ordered separately.
– PTC trip relay for switchboard mounting.
– IL and DL: 3 support feet and sundries for
base mounting.
– DL: Blind flange for repair purpose
4.4
Expected noise values as guideline
power of motor Sound pressure level pA [dB]
P N
[kW]
1450 min
< 0,55
0,75
1,1
1,5
2,2
3
4
5,5
7,5
11
15
18,5
22
30
1
)
Average area sound pressure level value
measured in a cubic area at a distance of 1
m to the motor surface.
ENGLISH
Pump with Motor
-1
2900 min
52
55
53
58
54
58
54
61
57
62
58
64
58
67
63
70
64
71
67
74
68
75
67
76
67
77
69
78
)
1
-1
13