Code
Description
Voltage U
DCfix
483
is outside of valid range
485
CAN transmission buffer is full
Class 5 Status
Class 5 status codes generally do not impair grid power feed operation, but can lead to lim-
Codes
itations in grid power feed operation. They will be displayed until the status code is ac-
knowledged by pressing a key (the inverter, however, continues working normally in the
background).
Code
Description
Insulation error on the solar
502
modules
No feed-in within the last 24
509
hours
515
No internal communication
with filter
516
Communication with memory
unit not possible
Power derating due to exces-
517
sive temperature
Function incompatibility (one
or more PC boards in the in-
558
verter are not compatible with
each other, e.g., after PC
board replacement)
Power derating due to over-fre-
560
quency
566
Arc detector switched off
(e.g., with external arc moni-
toring)
Details
for MPP2 string
Inverter does not feed energy
into the grid.
Inverter does not feed energy
into the grid.
Details
Warning message is shown on
the display.
Warning message is shown on
the display.
Warning message on the dis-
play
Warning message of memory
unit
If a power derating occurs, a
warning message is shown on
the display.
Possible error displays or mal-
functions in the inverter.
The status code is displayed
with excessive grid frequency.
The inverter reduces the pow-
er.
The status indicator is dis-
played until the inverter re-
sumes normal operation.
The status code is displayed
every day until the arc detector
is activated again.
Rectification
Check MPP settings;
If status code persists:
contact a Fronius-trained ser-
vice technician.
Carry out AC reset (switch au-
tomatic circuit breaker off and
on);
If status code persists:
contact a Fronius-trained ser-
vice technician.
Rectification
If this status code keeps recur-
ring, contact your system in-
staller.
Acknowledge status code;
check if all conditions for fault-
free grid power feed operation
are fulfilled (e.g., if the solar
modules are covered with
snow).
If the status code persists: ob-
serve further status codes.
If status code persists: Contact
a Fronius-trained service tech-
nician
If required, clean cool air vents
and cooling elements with
compressed air.
The fault is rectified automati-
cally.
If this status code keeps recur-
ring, contact your system in-
staller.
If this status code keeps recur-
ring, contact your system in-
staller.
As soon as the grid frequency
returns to the permissible
range and the inverter re-
sumes normal operation, the
error is rectified automatically.
If the status code persists,
contact your system installer.
No error!
Confirm status code displayed
by pressing the "Enter" key.
47