5.2
Technical data
Supply voltage
Current consumption
Terminal cross-section of all terminals
Max. ambient temperature
Protection class
Rel. humidity
Electromagnetic compatibility:
• Emitted interference
• Immunity to interference
Contact charge, signal contacts
• Collective fault signal
potentialfree changeover contact
• Single operation signal MA
potential-free normally open contact
• Single operation signal SL
potential-free normally open contact
Contact charge through control inputs
• "Ext. Off"
potential-free normally open contact
• "Control On"
potential-free normally open contact
• "Max. Speed"
potential-free normally open contact
• "Min. Speed"
potential-free normally open contact
Max. cable length per control input
Loop resistance per control input
Control input "Analogue In 0...10 V"
• Input resistance
• Overvoltage protection
PLR interface
• Max. cable length
• Min. cable cross-section
Tab. 2
5. 3 Scope of delivery
• AnaCon interface converter
• Installation and operating instructions
18
AnaCon
24 VDC ± 25%
85 mA
2
1.5 mm
+ 50°C
IP 20
Max. 95%, not condensing
EN 61000-6-3
EN 61000-6-2
Max. 250 VAC, 1 A
Min. 12 VDC, 10 mA
Max. 250 VAC, 1 A
Min. 12 VDC, 10 mA
Max. 250 VAC, 1 A
Min. 12 VDC, 10 mA
24 VDC, 2.4 mA
24 VDC, 2.4 mA
24 VDC, 2.4 mA
24 VDC, 2.4 mA
1000 m
Max. 480 Ω
> 200 kΩ
+/- 48 VDC
200 m
2
2x0.5 mm
WILO SE 04/2009