Idiomas disponibles

6.2.4 Priorities of the control contacts
• Tab. 6 shows the order of priority of the control contacts on the AnaCon
AnaCon
Control contact "off"
Control contact "max"
Control contact "min"
Control contact "on"
Tab. 6
6.2.5 Controls
"Mode" rotary switch
Fig. 1, item 14
"Setpoint" knob
Fig. 1, item 15
Button
Fig. 1, item 16
"Set" switch
Fig. 2, item 17
Tab. 7
Installation and operating instructions Wilo-Control AnaCon
AnaCon
Rotary switch for setting control mode:
• Δp-c for constant differential pressure
• Δp-v for variable differential pressure
• n-c for constant speed (manual control mode)
Setting the setpoint for the mode pre-selected with the "mode"
rotary switch (Fig. 4):
• Δp-c: 0 % = H
, 100 % = H
min
• Δp-v: 0 % = H
, 100 % = H
min
• n-c: 0 % = min. speed, 100 % = max. speed
The values H
, H
min
max
the pump type.
This button sends the settings made at the "mode" rotary
switch and at the "setpoint" knob to the pump connected (if the
pump was switched off, it will now be switched on).
The analogue input "0-10V" is released for each pump with this
switch:
• 0-10 V: release analogue input "0-10 V"
• disable: analogue input "0-10 V" blocked
Highest priority
Lowest priority
max
max
, min. speed and max. speed depend on