N
L
PE
+24 V
+24 V
+24 V
+24 V
Terminal
Type
Normally closed
NC
contact
C1
Common
Normally open
NO
contact
Normally closed
NC
contact
C2
Common
Normally open
NO
contact
10
DI3/OC1
4
With standard
product delivery,
AI1
analog inputs 1
and 2 are used by
the sensor.
2
DI1
12
NC
C1
NO
NC
C2
NO
OC
DI
+24 V
GND
10
4
+24 V/+5 V
2
+
+
5
6
A
Y
B
3
15
8
26
23
+24 V/+5 V
25
+
+
24
+5 V
7
Function
Signal relay 1. LIVE or PELV.
Signal relay 2. PELV only.
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
Analog input:
0-20 mA or 4-20 mA
0.5-3.5 V, 0-5 V or 0-10 V.
Digital input, configurable.
N
L
1
2
3
DI3/OC1
1
2
3
AI1
DI1
+5 V
GND
GENIbus A
GENIbus Y
GENIbus B
GND
+24 V
+24 V
+5 V
GND
GDS TX
GDS RX
AI2
Digital input 1 is factory-set to be start or stop input
where an open circuit results in stop. A jumper has
been factory-fitted between terminals 2 and 6. Re-
move the jumper if digital input 1 is to be used as ex-
ternal start or stop or any other external function.
4
4