Menu - Setup
Menu
Setup
Setup
The following reset functions are available:
Delivery status: Restores the parameter settings at the time of ship-
signal suppression or user-programmed linearisation curve, as well
as the measured value memory, are deleted.
Basic settings: Restores the parameter settings, incl. special param-
eters, to the default values of the respective instrument. Any stored
false signal suppression or user-programmed linearisation curve, as
well as the measured value memory, are deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
Menu item
Lock adjustment
Measurement loop name
Units
Probe length
Type of medium
Application
Medium, dielectric constant
Superimposed gas phase
Dielectric constant, upper medium (TS)
Tube inner diameter
Max. adjustment - Level
Min. adjustment - Level
Max. adjustment - Interface
Min. adjustment - Interface
6 Set up with the display and adjustment module
Default value
Released
Sensor
Länge der Messsonde factory set-
ting
Liquid
Level, vessel
Water-based, > 10
Yes
1.5
200 mm
100 %
Distance: 0.000 m(d) - note block-
ing distances
0 %
Distance: Probe length - take dead
band into account
100 %
Distance: 0.000 m(d) - note block-
ing distances
0 %
Distance: Probe length - take dead
band into account
41