en-us Installation
Seal the connection between transition and hood with
4.
aluminum tape. DO NOT use duct tape. Ensure that the
connection is completely sealed.
Remove the tape that is holding the damper closed.
5.
5 Installation
Installation
Installation
WARNING
Before installing, turn power OFF at the service panel.
Lock service panel to prevent power from being turned
▶
ON accidentally.
5.1 Installation height
Installation height above cooking surface:
Minimum height: 30" (762 mm)
¡
Suggested maximum height: 40" (1,016 mm)
¡
NOTICE:
Always follow the cooking appliance manufacturer's
installation instructions for proper installation height.
14
5.2 Cutout for vertical discharge
Vertical discharge installations require a cutout in the
ceiling to accommodate 10" (254 mm) duct and ⅝"
(16 mm) diameter clearance hole for ½" (12.7 mm) conduit
to the junction box.
X = Conduit zone
Hood size
30" (762 mm)
36" (914 mm)
42" (1067 mm)
48" (1219 mm)
54" (1372 mm)
60" (1524 mm)
5.3 Cutout for horizontal discharge
Horizontal discharge requires a wall cutout to provide
clearance for the transition. The location of the cutout is
determined by the hood installation height.
B
Back wall
C
Hood mounting heights:
30"– 40" (762 –1016) from cooking surface
X
21" (533 mm)
A
15" (381 mm)
18" (457 mm)
21" (533 mm)
24" (610 mm)
27" (686 mm)
30" (762 mm)