266 Technical data and references
Typical power cables
ACS880-
04-...
Cu cable type
2
mm
U
= 400 V
n
505A-3
3×(3×95)
585A-3
3×(3×120)
650A-3
3×(3×150)
725A-3
3×(3×185)
820A-3
3×(3×240)
880A-3
3×(3×240)
U
= 500 V
n
460A-5
3×(3×95)
503A-5
3×(3×95)
583A-5
3×(3×120)
635A-5
3×(3×150)
715A-5
3×(3×185)
820A-5
3×(3×240)
880A-5
3×(3×240)
U
= 690 V
n
330A-7
2×(3×95)
370A-7
2×(3×95)
430A-7
2×(3×95)
470A-7
3×(3×95)
522A-7
3×(3×120)
590A-7
3×(3×150)
650A-7
3×(3×150)
721A-7
3×(3×185)
1) The cable selection is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one on top
of the other, ambient temperature 30 °C (86 °F) PVC insulation, surface temperature 70 °C (158 °F) (EN 60204-1 and
IEC 60364-5-52). For other conditions, select the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.
2) The cable selection is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C (104 °F)
ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly buried).
For other conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive.
Terminal and entry data for the power cables
Maximum accepted
cable size
Screw size for connect-
ing busbars to the drive
module input and output
busbars
Tightening torque
1)
IEC
Al cable type
2
mm
3×(3×150)
2×500 MCM or 3×250 MCM
3×(3×185)
2×600 MCM or 3×300 MCM
3×(3×240)
2×700 MCM or 3×350 MCM
4×(3×185)
3×500 MCM or 4×300 MCM
4×(3×240)
3×600 MCM or 4×400 MCM
4×(3×240)
3×600 MCM or 4×400 MCM
3×(3×150)
3×(3×150)
2×500 MCM or 3×250 MCM
3×(3×185)
2×600 MCM or 3×300 MCM
3×(3×240)
2×700 MCM or 3×350 MCM
4×(3×185)
3×500 MCM or 4×300 MCM
4×(3×240)
3×600 MCM or 4×400 MCM
4×(3×240)
3×600 MCM or 4×400 MCM
2×(3×120)
2×(3×120)
2×(3×120)
3×(3×150)
3×(3×185)
2×500 MCM or 3×250 MCM
3×(3×185)
2×600 MCM or 3×300 MCM
3×(3×240)
2×700 MCM or 3×350 MCM
4×(3×185)
3×500 MCM or 4×300 MCM
2
4 × (3 × 240) mm
or 4 × (3 × 500 MCM)
M12
50...75 N·m (37...55 lbf·ft)
US
Cu cable type
AWG/kcmil
2×400 MCM or 3×4/0
2×300 MCM or 3×3/0
2×300 MCM or 3×3/0
2×350 MCM or 3×4/0
2×400 MCM or 3×4/0
2)
Al cable type
AWG/kcmil
2×700 MCM or 3×350 MCM
3×400 MCM or 4×250 MCM
3×400 MCM or 4×250 MCM
3×500 MCM or 4×300 MCM
3×700 MCM or 4×500 MCM
4×500 MCM
2×600 MCM or 3×300 MCM
2×700 MCM or 3×350 MCM
3×500 MCM or 4×300 MCM
3×600 MCM or 4×400 MCM
3×600 MCM or 4×400 MCM
4×500 MCM
4×500 MCM
2×350 MCM or 3×4/0
2×400 MCM or 3×4/0
2×500 MCM or 3×250 MCM
2×600 MCM or 3×300 MCM
2×700 MCM or 3×350 MCM
3×500 MCM or 4×300 MCM
3×500 MCM or 4×300 MCM
3×600 MCM or 4×400 MCM