Position the shelves.
14.Electrical connection - specialized technician -
BEFORE ANY OPERATION REMOVE VOLTAGE TO THE SYSTEM!
system must have a grounding connection!
The systems must be set up in accordance to the norms that regulate
manufacture, installation, use, and maintenance foreseen by the norms in
force in the country where the cabinet is installed.
ARNEG Spa declines any responsibility with regards to the user and third-
parties for damages caused by breakdowns or malfunctioning of the systems
installed upstream to the unit and for damages caused by the same due to
causes directly attributable to malfunctioning of the electrical system.
The cabinet must be protected upstream with an automatic, omnipolar
magneto-thermal switch having adequate characteristics and which will serve
as the main line disconnecting switch.
It is the Client's responsibility to arrange the electrical power supply line up to the
point of connection to the cabinet. Sizing of the electrical power supply line must be
performed in accordance to the power absorbed by the cabinet.
Remove all metallic objects worn: rings, watches, bracelets, earrings, etc.
Consult the wiring diagrams before performing the connection.
Instruct the operator on the position of the switch so that it may be timely reached
in case of an EMERGENCY.
14_1.Version with group incorporated:
The cabinet is prepared for plug connection (NOT SUPPLIED), install a plug with
suitable capacity for the electrical connection onto the power supply cable,
respecting the safety rules:
yellow-green = earth blue = neutral brown =phase
and in compliance with the national prescriptions in force
Make sure that the power supply cable is laid so that it can not be damaged and
cannot cause risk of injury to persons.
For the power supply lines measuring more than 4-5m, increase the section of the
cables appropriately.
Check that power supply voltage is the one reported on the rating plate.
To ensure normal operation, the maximum variation of the voltage must range
between +/- 6% of the nominal value.
Check that the power supply line has wires with an appropriate diameter, that it is
protected against overcurrents, and that the leakages to ground are in compliance
to the norms in force.
14_2.Version with group incorporated/remote:
The cabinet must be protected upstream with an automatic, omnipolar magneto-
thermal switch having adequate characteristics and which will serve as the main
line disconnecting switch.
The electrical system must have a grounding connection
First check that power supply voltage is the one reported on the rating plate(Rif. 2).
To ensure normal operation, the maximum variation of the voltage must range
between +/- 6% of the nominal value.
Check that the power supply line has wires with an appropriate diameter, that it is
protected against overcurrents, and that the leakages to ground are in compliance
to the norms in force.
The installer must provide the anchoring devices for all the wires in input and
output to/from the cabinet.
The automatic magneto-thermal switch must be such that it does not open the
circuit on the neutral, without simultaneously opening on the phases and, at any
05060155 00 28/11/2013
Ginevra 2
English
The electrical