Tighten the four screws until the thickness of the sponge seal, placed between the frame and the body of the unit, has
been reduced to 4-6 mm and the edge of the frame is substantially in contact with the false ceiling (a gap of under 5
mm):
U
8
C
U = body of the unit, C = frame, 8 = false ceiling
If there is still a gap between the frame and the false ceiling, it should be
reduced by working on the brace nuts and lock nuts again:
Replace the grille:
45°
Replace the covers at the four corners of the frame, making sure that you
secure the respective safety cords:
II. 2.3.4 Checking the correct installation of the frame-grille assembly (for all models)
The frame must not show signs of deformity caused by excessive traction. It
must be centered with respect to the false ceiling and, above all, it must
guarantee an airtight seal between the air inlet and outlet. The figure shows
the airtight seals (A-B), which prevent the air bypass (A) and treated air
leakage (B) inside the false ceiling. After installing the assembly, check that
the gap between the frame and the false ceiling is under 5 mm.
B
A
II. 2.4 EXTERNAL RENEWAL AIR AND TREATED AIR OUTLET IN AN
ADJACENT ROOM (FOR MODELS HCA1 60 , HCA1/4 60 ONLY)
The side openings made it possible to create a separate external renewal air inlet duct (5) and an air outlet duct in an
adjacent room (6).
50