v To confirm and go to the next parameter press F1.
v To leave press F6.
PT Second: (Power transformer secondary)
v
Utilize the increase or decrease keys to adjust the desired value for this variable.
v To confirm and go to the next parameter press F1.
v To leave press F6.
Connection: (Star or Delta connection type)
v
Utilize the increase or decrease keys to define if the connection will be Star or
delta.
v To confirm and go to the next parameter press F1.
v To leave press F6.
It is not necessary to change the tension or measurement system cables Star or
Delta the change is done by the PowerNET P-600 internal circuits.
Current sensor: (Current sensor set type)
v
Utilize the increase or decrease keys to define the utilized type.
Ø CT /R for rigid sensors or CT's adapter
Ø Flex for flexible sensors.
v To confirm and go to the next parameter press F1.
v To leave press F6.
Current sensor Type CT /R
Pliers model: (Selects the scale bottom of the utilized sensor 5, 100, 200, 1000,
2000, 3000 A)
v
Utilize the increase or decrease keys to define the utilized Model.
v To confirm and go to the next parameter press F1.
v To leave press F6.
Pliers scale: (Defines the range for the sensor: 100%, 50% or 20%)
v
Utilize the increase or decrease keys to define the utilized scale.
v To confirm and go to the next parameter press F1.
v To leave press F6
There are 3 scales for each Current sensor model CT /R type. For instance if
the Pliers model is 1000A and the desired measurement is not beyond 400A, then the
chosen scale for measurement is 50%. This way the current range utilized will be
500A improving the sensor performance
Flex Type Current sensor
v In this case it is only necessary to configure the Pliers model, the scales for the
flexible model are automatic, needs no previous configuration
Primary CT: (Current transformer Primary)
v Available for Current sensor type CT /R.
PowerNET P-600
Manual de Instalación y Operación
115