The PT Primary is defined as a Nominal tension. For instance, if was defined
the PT Primary as 220 Volts and a percentage equal to 10% then the range to
consider valids or invalids registries will be of 220V ± 10 %.
Tension temporary increase (EMT): event at which the effective tension value of
the system, momentarily increases to values above 10% the operation nominal tension,
during an interval of less than 3 seconds;
Tension temporary sinking (AMT): at which the effective tension value of the
system, momentarily falls to values below 90% the operation nominal tension, during
an interval of less than 3 seconds;
Inval Time: (Time to considerate EMT or AMT)
v Utilize the increase or decrease keys to define the time in seconds to considerate
valid or invalid registry.
v To confirm and go to the next parameter press F1.
v To leave press F6.
When detected a AMT or a EMT a time counter is fired, in the case that the
nominal tension value come back to normal before the time ends up, is registered an
event defining the registry as invalid, otherwise, the tension value will be a valid
registry . The invalid time value depends also of the configured value for registries
interval.
% Interruption: (defines lack of energy rate)
v Utilize the increase or decrease keys to define the interruption percentile value.
v To confirm and go to the next parameter press F1.
v To leave press F6.
This percentage defines below which nominal tension value it is considered lack
of energy or electrical energy interruption.
For instance, if it's configured as 20% the interruption percentile and if a
nominal tension measured is lower than this value, this registry will be considered as
invalid, independently of the time counter.
Considerations
Valid reading: tension obtained value reading without an interruption of
electrical energy event during the observed period. When having values registered
referring to the electrical energy interruption, sinkings and/or momentary tension
increases, the measurement interval of 10 (ten) minutes should be expurgated.
6.3. NETWORK ADDRESS, SERIAL COMMUNICATION, DISPLAY RATE and
LANGUAGE
Press the key F0 to activate the second function, when the display shows the
letter f at the lower right corner press F2. When the screen below is showed:
PowerNET P-600