6.4. INITIATING THE TENSION REGISTRIES
This function configures the PowerNET P-600 to start the registries in memory
when the tension goes beyond the maximum and minimum limits configured for the
event. This event is triggered by any one of the phases where the event is present first.
For instance, if a configuration is according the Chart 4 and the measured tensions are:
V1 = 240 V, V2=200 V and V3 = 256V, the PowerNET P -600 will start the registries in
memory, because an event occurs in phase 3.
Press the key F0 to activate the second function, when the display shows the
letter f at the lower right corner press F3. When the screen below is showed:
TN
Programa NUC = Program NUC 0
Cancela = Cancel
Allows the user to program one NUC (customer number). When configured a
NUC value, the equipment will create the registry area name with this value, in the
case that the NUC for program is "0", he utilizes the standard area name "AREA0001".
The keys "↑" and "↓" increase/decrease the value, and the keys "F1" and "F2" take the
cursor to left/right.
Press the keyF3 and the screen below will show:
TN
Habilita Evento = Enable Event
Cancela Evento = Cancel Event
In this screen you have 2 options:
PowerNET P-600
Phase
Event. Max
1
260
2
260
3
250
Chart 4
Manual de Instalación y Operación
Event.Min
180
180
180
119