Operating status
Start
Feed-in start
Feed-in mode with re-
duced power
No grid operation
Fault
Fault
6
Accessories
6.1
Inverter off
When using suitable KACO inverters, the shutdown can be carried out via the grid separation relay integrated into the
inverters and the "Inverter OFF" digital output instead of via interface switch.
Information about the "Inverter off" function: See manual under
egory "Hybrid and Battery Inverters".
7
Maintenance and troubleshooting
Repairs may only be carried out by the authorised electrician.
NOTE
Log all maintenance activities in the "Service" menu item: "Service Log" (exception: "User" interface). Con-
figuration is carried out via the web interface.
7.1
Visual inspection by the operator
1 Inspect the product and cables for visible external damage and note the operating status display, where applicable.
2 Notify the installer if there is any damage.
8
Cleaning
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
LED Icon
Description
The green "Operating" LED is on when the AC voltage is present, in-
dependent of the DC voltage.
If the LED is flashing, the internal communication between the compon-
ents is established. After flashing, the device is ready for feed-in.
If the LED continues to flash permanently, the internal communication
is interrupted.
The green "Operating" LED is lit.
The green "Grid operation" LED is lit after the country-specific
waiting period*.
Ready for grid operation. The charging/discharging current is displayed
via the WEB interface.
The interface switch engages audibly.
The green "Operating" LED is lit.
The green LED "Grid operation" is flashing because one of the modes:
internal power reduction, external power reduction, idle power request
or standalone mode is active.
Ready for grid operation. The charging/discharging current is displayed
via the WEB interface.
The interface switch engages audibly.
The green "Operating" LED is lit.
No LED is lit.
Error on the device or AC/DC source
The red "Fault" LED is illuminated.
Error on AC/DC source
Conditional special cases:
There is no DC voltage present (e.g. DC isolator switch open)
DC voltage too low (< starting voltage)
DC voltage is present (> starting voltage), but communications con-
nection between the front end (operating unit) and back end (con-
trol unit) is faulty, or interrupted.