↻ Connection cable with 2 x 1 strands already on the device.
1 Unscrew the cable fitting [
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M10 ring cable lug [max. width b. 42 mm]
5 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [
W17 /
6 Screw the positive (+) cable end onto the DC+ fuse holder according to the po-
larity of the battery [
W16 /
7 Check secure fit of all connected cables.
8 Make sure that the polarity is correct, and that the inrush current is ensured at
max. 300A.
9 Tighten the cable fittings [
4.5
Inserting the overvoltage protection
Information on the overvoltage protection: See
Battery-inverter/manual" category.
4.6
Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second
ground connection. To this end, the threaded bolt on the underside of the device can be used.
↻ The device has been installed on the mount.
1 Strip the insulation from the equipotential bonding cable.
2 Furnish the stripped cable with an M8 ring cable lug.
3 Check that the connected cable is fitted securely.
» The housing is included in the equipotential bonding.
4.7
Connecting the interfaces
4.7.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe pro-
tection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
All interfaces are located on the communication circuit board (HMI board) inside the housing.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
W_46].
30 Nm ].
30 Nm]
W_46 /
10 Nm ].
http://www.kaco-newenergy.com/de/downloads
M10
42 mm
M10
Fig. 7: DC connection M version
in the "hybrid- and
1
Fig. 8: Additional grounding point
1 Earthing bolt
Page 9